IS 11697 : 1986 Guide for determination of lightning impulse electric strength of insulating liquids
UDC 621.315.615 : 621.317.333.6 | ETD 3 |
|
Reaffirmed 2021 |
1 Scope
1.1 This guide describes test methods for assessing the electricstrength of insulating liquids when subjected to standard lightningimpulse in a divergent field.
1.1.1 Two methods are suggested:
a) Method A is based on a step-by-step procedure to provide anestimate of the impulse breakdown voltage under specifiedconditions; and
b) Method B is a statistically designed test to checkstatistical hypothesis about the impulse breakdown probability ofan insulating liquid at a given voltage level.
2 References
IS 2 :1960Rules for rounding off numerical values
IS 1876 :1961Method for voltage measurement by means ofsphere-gaps (one sphere earthed)
IS 2071 : Part 2 :1976 Methods of high voltage testing:Part 2 Test procedures
IS 2071 : Part 3 :1976 Methods of high voltage testing:Part 3 Measuring devices
IS 8090 :1976Specification for coupling, branch pipe, nozzleused in hose reel tubing for fire fighting
IS 9434 :1979Guide for sampling and analysis of free anddissolved gases and oil from oil-filledelectrical equipment