IS 15501 : 2004 Gaseous Fire Extinguishing Systems - IG 541 Extinguishing Systems
ICS 13.220.10 | CED 22 |
|
Reaffirmed 2015 |
1 Scope
1.1 This standard sets out specific requirements for the designand installation of total flooding fire extinguishing systemsemploying IG 541 gas extinguishant. This standard is applicable tosingle supply as well as distributed supply systems.
1.2 This standard complements various general requirementsapplicable to all types of gaseous fire-extinguishing systems(Halocarbon as well as Inert gas systems) listed in IS 15493. Assuch, both these standards should be read together before designinga system. Where requirements in both the standards differ, thisstandard shall take precedence.
1.3 Before using IG 541, nature of fire and fire spread shall bestudied for suitability of extinguishment as high discharge time of60 s may not be suitable for rapid spreading fires.
1.4 This standard covers systems operating at nominal pressuresof 15 MPa and 20 MPa only at 15 �C.
2 References
IS 7285 : 1988 Specification for seamless steel cylinders for permanent and high pressure liquefiable gases
IS 15493 : 2004 Gaseous fire extinguishing systems - General requirements