IS 15787 : 2008 Switch-Socket-Outlets (Non-Interlock Type)

ICS 621.31 6.541 ETD 14
Reaffirmed 2018

1 Scope

This clause of IS 1293 is applicable except asfollows:

Addition after the sixth paragraph:

This standard applies to fixed switched socket-outletswith out interlock for ac only, with or without earthingcontact, with rated voltage not exceeding 440V and arated current not exceeding 32A, intended forhousehold and similar purposes, either indoors oroutdoors.

Switched socket-outlets can also be produced bycombining a socket as per IS 1293 and a switch as perIS 3854.

2 References

This clause of IS 1293 is applicable, except asfollows:

Addition:

IS No.              Title
IS 302 : Part 1 : 2008 Safety of household and similar
electrical appliances: Part 1
General requirements (sixth revision)
IS 1293 : 2003 Plugs and socket-outlets of
rated voltage upto and including
250 volts and rated current upto
16 amperes (third revision)
IS 3854 : 1997 Switches for household and similar
fixed-electrical installation (second
revision)
IS 8828 : 1996 Circuit breakers for over current
protection for household and similar
installation (second revision)
IS 12640 Residual current operated circuit
breakers for household and similar
uses:
IS Part l : 2000 Circuit-breakers without integral
overcurent protection (RCCBs)
IS Part 2 : 2000 Circuit-breakers with integral
overcurent protection (RCCBS)
IS 14772 : 2000 Enclosures for accessories for
household and similar fixed
electrical installations