IS 15885 : PART 2 : SEC 3 : 2011 Safety Of Lamp Controlgear Part 2 Particular Requirements--Section 3 Ac Supplied Electronic Ballasts For Fluorescent Lamps

ICS 29.140.99 ETD 23

Reaffirmed 2016

1 SCOPE

This standard (Part 2/Sec 3) specifies particular safety requirements for electronic ballasts for use on ac supplies up to 1 000 V at 50 Hz with operating frequencies deviating from the supply frequency, associated with fluorescent lamps as specified in IS 2418 (Part 1) and IS 15687 (Part 2) and other fluorescent lamps for high-frequency operation.

Particular requirements for electronic ballasts with means of protection against overheating are given in Annex C.

Particular requirements for ac/dc supplied electronic ballasts for maintained emergency lighting are given in Annex K.

Performance requirements are covered in IS 13021 (Part 2).

2 REFERENCES

Following Indian Standards are necessary adjuncts to this standard:

2418 Tubular fluorescent lamps for general lighting service:

(Part 1) : 1977 Requirements and tests (first revision)

(Part 2) : 1977 Standard lamp data sheet (first revision)

9853 : 1981 Emergency lighting units

13021 (Part 2) : 1991 ac supplied electronic ballast for tubular fluroscent lamps: Part 2 Performance requirements

15885 (Part 1) : 2011 Safety of lamp controlgear: Part 1 General requirements

15687 (Part 2) Single-capped fluorescent lamps: Part 2 Performance requirements (under preparation)