IS 17345 : Part 1 : 2020 Power Track System - Part 1 General Requirement

ICS 29.060.10; 29.120.10 ETD 14

1 SCOPE

1.1 This Indian Standard (Part 1) specifies general requirements and tests for powertrack (PT) systems with a rated voltage not exceeding 240 V a.c. single phase with rated current not exceeding 20/25A, or 415 V a.c. two or three phase 50 Hz with a rated current not exceeding 73 A. These systems are used for distributing electricity in household, commercial and industrial premises.

1.2 Powertrack systems, according to this standard, are intended for use under the following conditions:

a) An ambient temperature in the range -5°C to +55°C, the average value over a 24 h period not exceeding 40 °C;

b) A situation not subject to a source of heat likely to raise temperatures above the limits specified above;

c) An altitude not exceeding 2 000 m above sea level;

d) An atmosphere not subject to excessive pollution by smoke, chemical fumes, prolonged periods of high humidity or other abnormal conditions.

In locations where special conditions prevail, as in ships, vehicles and the like and in hazardous locations, for instance, where explosions are liable to occur, special constructions may be necessary.

1.3 This standard does not apply to:

a) cable trunking systems and cable ducting systems covered by IS 14297 (Part 1);

b) busbar trunking systems covered by IEC 60439-2; and

c) electrical supply track systems for luminaires covered by IEC 60570.

2 REFERENCES

The following standards contain provisions, which, through reference in this text, constitute provisions of this standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties to agreement based on standard are encouraged to investigate the possibility of applying the most recent editions of the standards.