IS 18284 : 2023 Repair of Distribution Transformers - Code of Practice

ICS 29.180

ETD 16

New Standard from Last Update.

1. SCOPE

1.1 This code gives the guidelines along with tests including failure analysis and record keeping for the repair of liquid-immersed, dry-type, outdoor/indoor type, stacked core/wound core with CRGO or amorphous core material, double wound distribution transformers with nominal system voltages up to and including 33 kV and of the following types and ratings:

a) Liquid-immersed: Oil/Natural Ester/Synthetic- Organic Ester:

1) Three-phase ratings: up to and including 2 500 kVA (both sealed and non-sealed); and

2) Single phase ratings: up to and including 100 kVA (sealed type).

b) Dry-Type:

1) Three-phase ratings: up to and including 3 150 kVA; and

2) Single phase ratings: up to and including 100 kVA.

1.2 This standard does not apply to transformers which are excluded from the scope of IS 1180 series (see NOTE 1, Clause 1 of IS 1180 series standards).