IS 7098 : Part 3 : 1993 Cross-linked Polyethylene Insulated Thermoplastic Sheathed Cables - Specification - Part 3 : For Working Voltages from 66 kV up to and Including 220 kV
UDC 621.315.221.8 :678.073 ETD9
Reaffirmed 2019
1 Scope
1.1 This standard (Part 3) covers the requirements of single core, cross-linked polyethylene insulated, unarmoured or armoured (with or without lead alloy sheath) and thermoplastic outer sheathed cables for 3 phase ac earthed system for electric supply for the voltage grades given in Table 1.
| Table 1 Voltage Grades |
System Voltage | Rated Voltage | Highest System Voltage |
U(kV) | Uo/U (kV) | Um (kV) |
(1) | (2) | (3) |
66 | 38/66 | 72.5 |
110 | 64/110 | 123 |
132 | 76/132 | 145 |
220 | 127/220 | 245 |
1.2 Cables covered under this standard are suitable for use where the combined ambient temperature and temperature rise due to load result in conductor temperature not exceeding 90°C under normal operation and 250°C under short circuit operation.
2 References
IS 1885 : Part 32 : 1971 Electrotechnical vocabulary: Part 32 Cables, conductors and accessories for electricity supply
IS 5831 : 1984 PVC insulation and sheath of electric cables
IS 8130 : 1984 Conductors for insulated electric cables and flexible cords
IS 10810 Methods of test for cables:
Part 1 Annealing test for wires used in conductors
Part 3 Wrapping test for aluminium wires
Part 5 Conductor resistance test
Part 6 Thickness for thermoplastic and elastomeric insulation and sheath
Part 10 Loss of mass test
Part 11 Thermal ageing in air
Part 12 Shrinkage test
Part 14 Heat shock test
Part 15 Hot deformation test
Part 30 Hot set test
Part 32 Carbon content test for polyethylene
Part 34 Measurement of thickness of metallic sheath
Part 36 Dimensions of armouring material
Part 37 Tensile strength and elongation at break of armouring materials
Part 42 Resistivity test of armour wires and strips and conductance test of armour (wires/strips)
Part 53 Flammability test