IS 9482 : 1996 Single Sideband Power Line Carrier Terminals - Specification
ICS 29.240.20 : 35.180 | LTD 10 |
|
Reaffirmed 2020 |
1 Scope
1.1 This standard applies to Single Sideband (SSB) Power LineCarner (PLC) Termimls used to transmit information over HighVoltage (HV) Lines, and establishes recommended values forcharacteristic input and output quantities of single sideband PLCterminals (see Fig. 1) and definitions essential for anunderstanding of these recommendations.
1.2 This standard covers two versions of the PLC equipmentintended for two different applications as given below:
a) Standard Termmal - Equipment with a voice frequency sideinterface which offers transmission of a frequency band of 300 Hzto 3400 Hz on a four-wire basis plus sigmlling facilities. Thisequipment is capable via analog interafce, of being connected tonetworks that may consist of transmission equipment of differenttypes and from different manufacturers. There may be facilities foradditional point to point connection (for example, a teleprotectionconnection) which may fall outside the frequency band of 300 Hz to3400 Hz (see Fig. 2).
b) Spech-Plus Terminal - Equipment where specific interfaces forsignals like speech, data and teleprotection are present at thevoice frequency side (see Fig. 3).
The two versions will have parts in common and the requirementsof these common parts are dealt with under 6.2 and 6.3.1.
2 References
IS 1885 : Part 74 :1993Electrotechnical vocabulary:Part 74 Electrical and magnetic devices
IS 9528 : Part 2 :1980Manual for planning of (SSB) PLCSystems:Part 2 PLC Systems planning
IS 13736 : Part 3 : Sec 1 :1993 Classiilcation of environmentalconditions:Part 3 Classification ofgroups of environmental parameters andtheir severities,Section 1 Storage
IS 13736 : Part 3 : Sec 2 :1993 Classification of environmentalconditions:Part 3 Classification ofgroups of environmental parameters andtheir severities,Section 2 Transportation
IS 13736 : Part 3 : Sec 3 :1993 Classification of environmentalconditions:Part 3 Classification ofgroups of environmental parameters andtheir severities,Section 3 Stationary use atweatherprotectcd locations
IS 13968 : Part 1 :1994Performances and testing ofteleprotection equipment of powersystems:Part 1 Narrow-band commandsystems